The Commercial RiserPACK Model 8511 is a riser assembly designed for NFPA 13 fire sprinkler systems that require pressure relief.

The Model 8511 includes a flow switch, TESTanDRAIN Model 2511A, Model 7600 3-way Globe Valve, a M7500 Pressure Gauge and features a hose test connection. The Model 8511 can also be fitted with an optional pressure reducing valve (see PRV options below).

RiserPACK M8011
M8511 Base Model Item ID Orifice Size Size Connection
8530 3/8" Orifice 1 1/2" Groove X Groove
8531 7/16" Orifice
8532 1/2" Orifice
8533 17/32" Orifice
8534 5/8" ELO Orifice
8540 3/8" Orifice 2" Groove X Groove
8541 7/16" Orifice
8542 1/2" Orifice
8543 17/32" Orifice
8544 5/8" ELO Orifice
8560 3/8" Orifice 2 1/2" Groove X Groove
8561 7/16" Orifice
8562 1/2" Orifice
8563 17/32" Orifice
8564 5/8" ELO Orifice
8565 3/4" ESFR Orifice
8570 3/8" Orifice 3" Groove X Groove
8571 7/16" Orifice
8572 1/2" Orifice
8573 17/32" Orifice
8574 5/8" ELO Orifice
8575 3/4" ESFR Orifice
8580 3/8" Orifice 4" Groove X Groove
8581 7/16" Orifice
8582 1/2" Orifice
8583 17/32" Orifice
8584 5/8" ELO Orifice
8585 3/4" ESFR Orifice
8586 K25 Orifice
8590 3/8" Orifice 6" Groove X Groove
8591 7/16" Orifice
8592 1/2" Orifice
8593 17/32" Orifice
8594 5/8" ELO Orifice
8595 3/4" ESFR Orifice
8596 K25 Orifice

Pressure Reducing Valves

Pressure Reducing Valves (PRV) regulate water pressure entering the fire protection system from the main water supply.

Field Adjustable PRV (1 1/2" & 2")

Field Adjustable Pressure Reducing Valves regulate incoming water pressure and can be adjusted in the field.

Field Adjustable Pressure Reducing Valves

Generating an Item ID:
First, choose the desired Manifold: 8530- Then, choose the desired PRV: FA-ZW-AB. Example Item ID: 8530-FA-ZW-AB

8511 Size Item ID Orifice Size Zurn Wilkins Elkhart Brass
Inline Body Angled Body Inline Body Angled Body
1 1/2" 8530 3/8" Orifice FA-ZW-AB
8531 7/16" Orifice FA-ZW-AB
8532 1/2" Orifice FA-ZW-AB
8533 17/32" Orifice FA-ZW-AB
8534 5/8" ELO Orifice FA-ZW-AB
2 1/2" 8560 3/8" Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB
8561 7/16" Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB
8562 1/2" Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB
8563 17/32" Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB
8564 5/8" ELO Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB
8565 3/4" ESFR Orifice FA-ZW-IL FA-ZW-AB FA-EB-IL FA-EB-AB

Pilot Operated PRV (2", 2 1/2", 3", 4" & 6")

Pilot Operated Pressure Reducing Valves regulate incoming water pressure.

Pilot Operated Pressure Reducing Valve

Generating an Item ID:
First, choose the desired Manifold: 8560- Then, choose the desired PRV: PO-ZW-IL. Example Item ID: 8560-PO-ZW-IL

8511 Size Item ID Orifice Size Zurn Wilkins
Inline Body
2" 8530 3/8" Orifice Call for Availability
8531 7/16" Orifice
8532 1/2" Orifice
8533 17/32" Orifice
8534 5/8" ELO Orifice
2 1/2" 8560 3/8" Orifice PO-ZW-IL
8561 7/16" Orifice PO-ZW-IL
8562 1/2" Orifice PO-ZW-IL
8563 17/32" Orifice PO-ZW-IL
8564 5/8" ELO Orifice PO-ZW-IL
8565 3/4" ESFR Orifice PO-ZW-IL
3" 8570 3/8" Orifice PO-ZW-IL
8571 7/16" Orifice PO-ZW-IL
8572 1/2" Orifice PO-ZW-IL
8573 17/32" Orifice PO-ZW-IL
8574 5/8" ELO Orifice PO-ZW-IL
8575 3/4" ESFR Orifice PO-ZW-IL
4" 8580 3/8" Orifice PO-ZW-IL
8581 7/16" Orifice PO-ZW-IL
8582 1/2" Orifice PO-ZW-IL
8583 17/32" Orifice PO-ZW-IL
8584 5/8" ELO Orifice PO-ZW-IL
8585 3/4" ESFR Orifice PO-ZW-IL
8586 K25 Orifice PO-ZW-IL
6" 8590 3/8" Orifice Call for Availability
8591 7/16" Orifice
8592 1/2" Orifice
8593 17/32" Orifice
8594 5/8" ELO Orifice
8595 3/4" ESFR Orifice
8596 K25 Orifice

Factory Set PRV (1 1/2" & 2")

NOTE: When choosing a Factory Set Pressure Reducing Valve, you must choose a Bonnet that corresponds with your application's specifications (refer to chart below).

Factory Set Pressure Reducing Valves regulate incoming water pressure and come pre-configured from the factory.

Factory Set Pressure Reducing Valves

Generating an Item ID:
First, choose the desired Manifold: 8530- Then, choose the desired PRV: FS-ZW-AB-. Lastly, choose the appropiate Bonnet (refer to charts below): N. Example Item ID: 8530-FS-ZW-AB-N

8511 Size Item ID Orifice Size Zurn Wilkins Wilson & Cousins
Inline Body Angled Body Inline Body Angled Body
1 1/2" 8530 3/8" Orifice FS-ZW-AB-__ FS-WC-AB-__
8531 7/16" Orifice FS-ZW-AB-__ FS-WC-AB-__
8532 1/2" Orifice FS-ZW-AB-__ FS-WC-AB-__
8533 17/32" Orifice FS-ZW-AB-__ FS-WC-AB-__
8534 5/8" ELO Orifice FS-ZW-AB-__ FS-WC-AB-__
2 1/2" 8560 3/8" Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__
8561 7/16" Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__
8562 1/2" Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__
8563 17/32" Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__
8564 5/8" ELO Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__
8565 3/4" ESFR Orifice FS-ZW-IL-__ FS-ZW-AB-__ FS-WC-IL-__ FS-WC-AB-__

Choosing the proper Bonnet:
When choosing the Bonnet for the Pressure Reducing Valve refer to the charts and the following procedure:

  1. Determine the demand in gallons per minute required downstream of the valve.
  2. To determine the static outlet pressure, locate the static chart. Determine the valve inlet static pressure shown on the vertical axis and draw a horizontal line from that pressure to the appropriate curve determined above. Then, draw a vertical line down to the horizontal axis and read the static outlet pressure.
  3. Determine the standpipe residual or "flow pressure" at the valve inlet.
  4. Locate the appropriate flow chart based on GPM required and body style.
  5. Locate the inlet residual pressure on the vertical axis of the chart and draw a horizontal line from this pressure across the chart.
  6. Locate the desired valve outlet residual pressure on the horizontal axis of the chart and draw a vertical line from this pressure.
  7. The curve nearest the intersection of the two drawn lines is the appropriate type for the valve.

Click on image to enlarge.

RiserPACK M8011